PowerPro Hardware Specifications
Voltage V1, V2, V3
VN
0 - 600 VAC
0 - 600 VAC / 1000VDC
or
0 - 80VAC / 120VDC
Current CT1, CT2, CT3
CT4
1 - 3000A AC
1 - 3000A AC/DC
Frequency 31 - 65 Hz
31 - 450 Hz (VIP400 firmware Option)
Accuracy Voltage: 0.2% of full scale
Current: 0.2% of full scale
Sampling 256 samples / cycle every cycle
Storage Rate 1 second to 30 minutes
Power Supply Internal from V1 (70V to 600V) or external AC/DC adapter
Battery Backup 5 hrs run time. Data backup infinite
Memory 1G removable memory cards
Operating
Temperature
-20°C to 60°C
Weight 3.73Kg, 10 lb
Size (L)10.5" x (W)10" x (H)7"
Safety 600V CAT IV
 
*Specifications subject to change without notice

PowerPro Specifications - PDF (0.99MB)
 
Firmware feature
RMS Data
  • Min, Max and Average RMS data storage.
  • Updates Min, Max and Average RMS data every cycle.
Connection Type
  • 1P2W, 1P3W, 3P3W, 3P4W, 2.5Element
Power Calculations
  • KW,KVA, KVAR, total and per phase Demand.
  • Updates power calculations every cycle.
  • True Power Factor, KW divided by KVA.
Event Capture
  • Stores current and voltage data during voltage sag or swell.
Current Inrush
Spike Detect
  • Voltage transients as fast as 65 microseconds are captured.
  • Stores current and voltage data during voltage transient.
  • Spike Detect Application Note (PDF - 818KB)

Firmware options

 

View PDF files with Adobe Acrobat Reader version 4.0 or later,
click icon to download a free copy.

 

 
Copyright © 2000 - 2010, Candura Instruments. All Rights Reserved.